Permit: T05CM05879

Parcel: 141148150


Addresses:

9050 E VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM05879

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED LETTER DELETING ROOF CANOPY AND RAIN DRAINS ON NORTH SOUTH CANOPIES -- (303) 525-9352
06/27/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE PLUMBING WORK PROVIDE BACK FLOW VERIFICATIONS
2) PROVIDE ACCESS TO CLEANOUTS IN MEAT AND SEAFOOD SINKS (2)
06/06/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE INSULATION ON HOT PIPING PER PLAN.
2. PROVIDE BACKFLOW PROTECTION ON HAND SPRAYER WITH CERTIFICATION AT PAN WASHER.
3. PROVIDE BACKFLOW PROTECTION FOR ICE MACHINE & POTABLE WATER TO SODA DISPENSER WITH CERTIFICATION.
4. SUPPORT WATER PIPING ON OVENS AND REMOVE ALL DEBRIS.
06/05/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
03035 -- WATER PIPING IN BAKERY OK
NEED INSULATION ON HOT PIPING IN BAKERY.
03090 -- PARTIAL FOR FIXTURES IN BAKERY ONLY GAS SYSTEM SHALL BE COMPLETE & TESTED & APPROVED BY ALL CONCERNED TO OCCUPY THIS AREA.
05/16/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
MEAT BOX & MEAT ROOM INTERMEDIATES FINAL OK
PENDING CITY APPROVAL OF REVISED YET TO BE APPROVED PLAN.
DATE 5/4/06 RICHARD JOACHIM
04/20/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
STARBUCKS 3-COMP SINK DRAIN, SANITIZE BOWL TO BE SEPARATE DRAIN FROM WASH & RINSE DRAIN.
PHARMACY WATER HEATER REQUIRES CORRECT SUPPORT FOR PAN DRAIN A T&P TO GRAVITY DRAIN TO FLOOR SINK.
(3) IN HOUSE BACKFLOW CERTIFICATIONS FOR STARBUCKS.
04/19/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/17/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE INSPECTION OF CONTINUATION OF WATER PIPING FOR STARBUCKS, SUPPORTED CORRECTLY TO POINT OF CONNECTION.
2. DRAINS FROM APPLIANCES TO BE GRAVITY, RIDGID PIPING SEPARATE DRAINS.
3. PROVIDE BACKFLOW PROTECTION FOR ICE MACHINE, ESPRESSO MACHINES, COFFEE MAKERS, WITH CERTIFICATIONS.
4. PROVIDE SEPARATE DRAINS FOR ICE BIN & MAKER IF REQUIRED FROM ICE MAKER.
5. FAUCET FOR 3-COMP SINK TO HAVE BACKFLOW PROTECTION OR CORRECT MEANS TO PROVIDE NO SUBMERGED INLET FOR HAND SPRAYER.
6. PLEASE PROVIDE LISTING SHEET FOR R.O. UNIT.
04/10/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
FLORAL AREA OK