Permit: T05CM05879

Parcel: 141148150


Addresses:

9050 E VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM05879

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 10 PSI TEST FOR COOK LINE IN DELI OK
2) RECEIVED (3) IN HOUSE BACK FLOW CERTIFICATIONS FOR DELI AREA
3) NEED COMPLETION OF MISSING HAND SINKS IN DELI UPON APPROVAL
4) NEED CORRECT DRAINAGE FOR COMBI-OVENS
5) NEED CORRECT AIR GAP FOR EXISTING 1/2" DRAIN AND 1 1/2 DRAIN BEHIND SOUTH FRYER
06/27/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE TEST ON GAS PIPING IN DELI
2) PROVIDE REVISED APPRIOVED PLAN FOR GAS TO WASHER BOOSTER HEATER IN DELI
06/19/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1 1/4 GAS TO MAV-1 PRESSURE TEST OK
1. PROVIDE CSA OR AGA APPROVED GAS VALVES AND INSTALL PIPING FOR GAS ISOMETRIC FOR COOKING.
06/06/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
CONNECTION TO METER NEW PIPING OK
1. SUPPORT PIPING AT METER PROP.
06/05/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
5 PSI TEST THRU ANSUL VALVE INSTALLED AT DONUT FRYER OR BACK TO METER OK
15 PSI TEST FOR PAN.
05/31/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
2" BLK OVERHEAD FROM METER AREA TO (2) OVENS, (1) DONUT FRYER AND MVA ON ROOF 15 PSI TEST (PARTIAL APPROVAL) NEED RETEST WHEN ANSUL VALVE & ALL VALVING IS INSTALLED. SUPPORT & SECURE ALL PIPING CORRECTLY.