Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | PLUMBING - INTERMEDIATE | Approved | OK TO COVER ALL AREAS | |
| 11/17/2006 | PLUMBING - INTERMEDIATE | Approved | CORRECTIONS MADE OK OK TO COVER ALL AREAS. |
|
| 11/15/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT TRAP ARMS. 2. SECURE CLOSET FLANGES TO THE FLOOR. SEE NOTE #5 ABOVE. (11/8/06 INSP.) 3. TUBS TESTED TO BOTTOM OF OVERFLOW ONLY. SEE NOTE #3 ABOVE. (11/8/06 INSP.) |
|
| 11/08/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLAN SPECS 3/4 HW. CW TO LAUNDRY. CAST IRON FITTINGS NOT REQUIRED IF USED, PROPER TRANSITION COUPLINGS SHALL BE USED 2) SWEEPS REQUIRED ON TRAP ARM CHANGE OF DIRECTION 3) PROVIDE TEST ON TUB OVERFLOW 4) PROVIDE PRESSURE GAUGE ON WATER PIPING 5) CLOSET FLANGES SHALL BE FASTENED TO FLOOR 6) NON FERROUS PIPE NIPPS REQUIRED AT NON FURROUS HOUSE BIB CONNECTIONS (CAN BE INSTALLED AT FINAL) |