Permit: T05CM05814

Parcel: 11107105C

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/28/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
- USE THE ADHESIVE SEALANT ON YOUR ARMORFLEX TO COMPLETE THE JOB.
- PLEASE INSTALL HB VAC BREAKERS OR REMOVE HBS
- IN THE FUTURE I THINK THAT BOXING OUT FOR TUB P TRAPS WOULD BE BEST WHEN IN FOOTING.
09/27/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
3 OF THE 4 TUB P-TRAPS INSTALLED IN THE FOOTING HAVE BLACK PIPE SHOWING, ALSO THE TRAP ARMS INSTALLED THROUGH YOUR FOOTINGS SHOULD HAVE A THICKER WRAP, CODE DOES CALL FOR PIPING IN FOOTINGS TO BE SLEEVED.
ALSO, POLY SLEEVING IS LISTED FOR USE ON METALLIC PIPES. PLASTIC PIPING EXPANDS AND CONTRACTS AT A MUCH HIGHER RATE. MY AQUA PEX BOOK HAS A PICTURE OF A RIGID SLEEVE OR ARMORFLEX.
09/19/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
OK TO BACKFILL
RECALL ROUGH PLUMBING INSPECTION PRIOR TO CONCRETE.
POLY SLEEVING NOT ADEQUATE PROTECTION OF PEX TUBING PENETRATING SLAB. REFER TO PEX INSTALLATION INSTRUCTIONS.