Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STILL HAVE SHARED NEUTRAL TERMINATION IN BOTH PANELS - NEC 408.21 ALSO, WHEN Y0U REARRANGED CONDUCTORS ON GROUND BAR 2. DIFFERENT SIZED GROUNDS NOT TO BE UNDER SAME SET SCREW 3. HAVE INSULATION INSTEAD OF CONDUCTOR UNDER SET SCREW 4. HAVE SEVERAL LOOSE SET SCREWS - REINSPECTION FEE IF NOT CORRECT NEXT TIME. |
|
| 03/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEUTRAL NOT TO TERMINATE WITH ANOTHER CONDUCTOR IN PANEL -- NEC 408.21 2. INSTALL BLANK COVER @ KITCHEN COUNTER J-BOX -- NEC 110.12A 3. PROVIDE CONNECTOR FOR ROMEX INTO HOOD - NEC 300.16 4. PROVIDE ROOF ACCESS 5. ROOF SERVICE RECEPTACLE COVERS WON'T OPEN. |