Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/16/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STAPLES AT UFER (REPEAT) 2) SCREWS AT FHA (REPEAT) 3) FIRE STOP FIRE PLACE 4) FIRE BLOCK AT SGD 5) SECURE WIRES 8" FROM BOX AT ENTRY 6) BLOCK MECH 3 SIDES 7) STOPPED INSPECTION-NOT READY |
|
| 03/15/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE STAPLES FROM UFER/DIS-SIMILAR METALS 2) CHANGE SCREWS IN FHA STRAPS TO NAILS 3) BANG PLATE EAST SIDE OF DRYER VENT 4) CREATE 1" CLEARANCE TO B-VENT 5) BLOCK PLENIUM 3 SIDES 6) NEED SOFFIT AT FRESH AIR DUCT 7) BLOCK DUCT BOOTS 3 SIDES 8) CAULK GARAGE LIGHTS, ALL FASCIA-FOAM INTERSECTIONS 9) STOPPED INSPECTION AT GARAGE |
|
| 03/14/2006 | FRAMING | Cancelled | CANCELLED PER TITO OF HSP | |
| 03/13/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER SUPER |