Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05707
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2006 | ELECTRIC - FINAL | Approved | ||
05/25/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/23/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE OBJECTIONABLE CURRENT ON BONDING CONDUCTORS NEC 250.6 2. EMERGENCY LIGHTING NOT PER PLAN. 3. INSPECTION TO CONTINUE -- THIS REPORT IS PARTIAL |
|
05/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL ONLY IN ELECT. ROOM 1. 2/0 COPPER UFER TO 112 1/2 KVC TRANS CONNECTED TO FRAME OF TRANSFORMER NEEDS A MAIN BONDING JUMPER TO NEUTRAL. NEW NEUTRAL OFF SYSTEM NEEDS TO BE GROUNDED, NEUTRAL FROM 480 VOLTS SYSTEM SHOULD NOT BE CONNECTED TO TRANSFORMER NEUTRAL BAR. 2. PANEL A CIR'S 13 & 15 USED NOT ON DIRECTORY. 3. PANEL SCHEDULE HPP - MARK MAIN FOR TRANSFORMER. 4. PANEL LDP - NEUTRALS TO BE WHITE - NOT BOTH GRAY & WHITE. 5. PANEL B SCHEDULE ON PLAN HAS QUITE A FEW MORE CIRCUITS THAN ACTUAL SCHEDULE, BOND LUG ON BOTTOOM NIPPLE LOOSE. |