Permit: T05CM05393

Parcel: 119420850

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
01/03/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
1) PROVIDE SHEAR REVISION FOR GARAGE SHEAR
12/29/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RAT RUNS NOT INSTALLED
2) SHEAR TRANSFER NOT PER PLAN-3 PLACES
3) PARTITION CHANNELS NOT NAILED PER PLAN
4) SHIM 3 POINT BEARING AT BACK GIRDER
12/29/2005 EXT METAL CLIPS/EXT SHEATHING Denied 1) BRACING NOT PER CALC'S
2) #3 SHEAR MISSING NAILS
3) WIND BRACE MISSING NAIL
4) NAIL PROTECT PLUMBING FROM OUTSIDE
5) COMPLY WITH DETAIL 524 SD
6) PROVIDE DETAIL FOR ENTRY TOWER FRAMING NOT PER PLAN
12/22/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MASS STRAP NOT NAILED
2) SHEAR IN FRONT OF GARAGE NOT NAILED
3) REPLACE DAMAGED CLIPS
4) ROOF BEING NAILED
5) EXTERIOR STUDS MISSING SOUTH EAST WALL
6) STOPPED INSPECTION