Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/15/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/06/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) COPPER PIPING UNDERGROUND FOR YARD WATER OK |
|
| 01/30/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SEE ALL NOTES FROM 12/28/06 INSPECTION & COMPLY FAILURE TO COMPLY SHALL RESULT IN REFEE HAVE AN APPROVED PLUMBING PLAN ON SITE. |
|
| 01/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE APPROVED PLANS FOR ONE RESTROOM |
|
| 12/28/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) WATER TEST WASTE AND VENT THRU ROOF OK 2) PROVIDE TEST ON WATER PIPING 3) PROVIDE FHA STRAPS TO PROTECT DWV AT FLOOR COVER 4) SHALL PROVIDE REVISED CITY APPROVED PLAN FOR CHANGE FROM WATER HEATER TO INSTA HOT WATER HEATER 5) NOTE: INFORMED OWNER ABOUT RESTROOM ISSUE, THIS IS BEING HANDLED BY BLDG OFFICIAL |
|
| 12/22/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) REPAIR LEAK ON ABS PIPING BEFORE CALLING FOR INSPECTION 2) B-OCCUPANCY 2016 SP. FT REQUIRES 2 RESTROOMS PER SECTION 2902.2 OF 2003 IBC |
|
| 09/08/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* POST AN ADDRESS AT YOUR SITE. AND HAVE INTERMEDIATE WORK COMPLETE & UNDER TEST. |