Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY LIGHTING TO BE ENERGIZED BY NORMAL LIGHTING CKT FOR THAT AREA -- NEC 700.12 2. EMERGENCY LIGHTING TO BE PER PLAN 3. RECEPTACLES WITH METAL FACE PLATE TO EXTEND PAST FACE PLATE -- NEC 406.4 D 4. PANEL DIRECTORY TO BE CORRECT, NEAT, LEGIBLE NEC 408.4 |