Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM05355

Parcel: 105101270


Addresses:

450 E WETMORE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EMERGENCY LIGHTING TO BE ENERGIZED BY NORMAL LIGHTING CKT FOR THAT AREA -- NEC 700.12
2. EMERGENCY LIGHTING TO BE PER PLAN
3. RECEPTACLES WITH METAL FACE PLATE TO EXTEND PAST FACE PLATE -- NEC 406.4 D
4. PANEL DIRECTORY TO BE CORRECT, NEAT, LEGIBLE
NEC 408.4