Permit: T05CM05203

Parcel: 10606031D


Addresses:

1020 W PRINCE RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/21/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/18/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS
2. PAINT EXPOSED PVC W/LATEX PAINT
3. AIR BALANCE OK
4. PROVIDE CONDUIT FOR LOW VOLTAGE WIRES
5. REMOVE SINGLE WALL SECTION OF WATER HEATER VENT FROM ROOF.
6. RUN CONDENSATE FROM SMALL UNIT INTO APPROVED DRAIN. SECURE AS NEEDED. TESTED DUCT SMOKE DETECTORS.
12/07/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DUCT SMOKE DETECTORS W/AUDIBLE & VISIBLE ALARMS.
2. EXTEND WATER HEATER VENT 2' ABOVE WALL ON ROOF.
3. VENT ON WATER HEATER NOT CORRECT.
4. PROVIDE GREASE CUP.
5. PROVIDE AIR BALANCE REPORTS.
6. INSULATE REFER LINES ON ROOF.
7. LOW VOLTAGE WIRE ON ROOF MUST BE IN CONDUIT.
8. PROVIDE FRESH AIR INTAKES
9. PROVIDE CONDENSATE DRAINS