Permit: T05CM05203

Parcel: 10606031D


Addresses:

1020 W PRINCE RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/06/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
1. CORRECTIONS MADE OK
2. PLUMBING FINAL OK
3. OK FOR C OF O S.T.O.I
11/29/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. ALL ROOF DRAINS TO BE CLEARED OF DEBRIS AND INSTALL STRAINER AND COVERS.
2. VENTS LESS THAN TEN FEET FROM AIR INTAKES TO BE EXTENDED 3' ABOVE.
3. PAINT ALL VENTS WITH LATEX PAINT.
4. REMOVE ALL ABANDONED PIPING
5. USE BLIND PLUG AT ABANDONED WATER CLOSET.
6. I.W PIPING BETWEEN 5-15 FEET TO BE DIRECTLY TRAPPED IW PIPING TO BE GRAVITY DRAIN AND SUPPORTED.
7. TRAP AND TRAP ARM TO BE SAME SIZE.
8. INSTALL STRAINERS AND GRATES FROM FLOOR SINKS.
9. IW PIPING TO HAVE AIR GAP.