Permit: T05CM05203

Parcel: 10606031D


Addresses:

1020 W PRINCE RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/10/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
06/26/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. PLUMBING AT WATER CLOSETS NEEDS TO BE REDONE OK TO COVER ALL OTHER AREAS -- UNDERGROUND ONLY
2. GAS PRESSURE TEST OK
03/13/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. PLEASE RE-POST YOUR ADDRESS
2. NOT READY FOR INSPECTION
3. DBL COMBO MAY NOT LAY ON ITS BACK HORIZ. VENTING BELOW FLOOD RIM LIMITED TO STRUCTURAL CONDITIONS
4. PIPING TO BE LAIN ON A FIRM BED.
5. 2 WAY CLEANOUT FITTING UNDER SLAB FOR TEST NOT APPROVED.
6. TEST ENTIRE UNDERGROUND. IF THERE IS A PROBLEM WITH THE EXISTING DON'T YOU WANT TO KNOW ABOUT IT NOW RATHER THAN LATER?
02/15/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*3" floor sink w/ cast iron p trap w/trap primer at meat case location ok water tested to 10'
02/14/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TRANSITION FROM CAST IRON FLOOR SINK TO ABS REQUIRES A MISSION COUPLING OR USE CAST IRON BETWEEN CAST IRON P TRAP & FLOOR SINK.
- PROVIDE A 10' WATER TEST
- PROVIDE PERM CAP AND CAPPABLE TEST WYE AT TEST WYE
LOCATION
02/13/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MISSION COUPLING REQUIRED AT TRANSITIONS FROM CAST IRON TO PLASTIC
N/H COUPLING OK AT CAST TO CAST
PROVIDE WATER TEST ON NEW PIPING.
01/29/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*PLEASE RE POST YOUR ADDRESS
PLAN IS NOT REFLECTIVE OF THE INSTALLATION, NEW 3" FLOOR SINK IS EXISITING, WITH NO VENT. HANDSINK IS EXISTING WITH EXISTING FLOOR SINK BELOW ( NOT SHOWN ON THE PLAN)
PLEASE CLARIFY THE PLAN TO SHOW ALL NEW, AND ALL EXISTING PLUMBING
VENT CONNECTED TO HORIZONTAL DRAIN TO HAVE ITS INVERT ABOVE DRAINAGE CENTER LINE.
FURNCO NOT PERMITTED
N/H BANDS NOT PERMITTED
REINSPECTED
NUMBER FIVE ABOVE CORRECTEDNUMBER FOUR ABOVE CORRECTED
OK TO COVER TO 3" FLOOR SINK