Permit: T05CM05118

Parcel: 107031890

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/16/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES.
LEAVE OUT UNDER FAN COIL.
PROVIDE 15 AMP BREAKER FOR FAN COIL
DUCT INSULATION OK
03/07/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TERMINATE SECONDARY DRAIN TO A CONSPICUOUS LOCATION OR USE AN OVERFLOW SENSOR. TRAP ON SECONDARY NOT REQUIRED.
2. PLANS APPROVED IN ERROR, 1" DUCT LINER NOT ADEQUATE. PROVIDE MIN. R5 DUCT LINER & FOIL WRAP.
3. RELOCATE HANGER ROD & REFER LINE FROM BLOCKING ACCESS TO SERVICE FAN COIL.
4. OK TO INSULATE CONDENSATE DRAIN.