Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES. LEAVE OUT UNDER FAN COIL. PROVIDE 15 AMP BREAKER FOR FAN COIL DUCT INSULATION OK |
|
| 03/07/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TERMINATE SECONDARY DRAIN TO A CONSPICUOUS LOCATION OR USE AN OVERFLOW SENSOR. TRAP ON SECONDARY NOT REQUIRED. 2. PLANS APPROVED IN ERROR, 1" DUCT LINER NOT ADEQUATE. PROVIDE MIN. R5 DUCT LINER & FOIL WRAP. 3. RELOCATE HANGER ROD & REFER LINE FROM BLOCKING ACCESS TO SERVICE FAN COIL. 4. OK TO INSULATE CONDENSATE DRAIN. |