Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1. EXHAUST DUCTS UPSIDE DOWN 2. INSTALL LOW VOLTAGE WIRES PER NEC 3. OK TO SHEETROCK RESTROOMS 4. WILL CHECK ON ABOVE CEILING INSPECTION 5. SECONDARY DRAIN PAN MUST BE MIN. 1 1/2" LARGER ON ALL SIDES OF FAN COIL. |