Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2007 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
| 03/05/2007 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE UFER COVERED WITHOUT APPROVAL - SUPPLEMENT SERVICE WITH GROUND RODS OR OTHER APPROVED GROUNDING ELECTRODE. 2. PROVIDE LETTER OF TORQUE FOR SERVICE. 3. PROVIDE REVISED SINGLE LINE DIAGRAM FOR SERVICE THAT INCLUDES ALL LOADS. 4. PROVIDE PROTECTION FOR CONDUCTORS -- NEC 300.4 |