Permit: T05CM04759

Parcel: 11006159B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/20/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECT LEAKING HB ON SOUTH SIDE
UNITS 33, 34, 35 AND 36 FINAL APPROVED
12/18/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLEASE CALL IN AND HAVE APPROVED, ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL
09/24/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNIT #38 APPROVED
33-36 KS MISSING CLEANOUT
08/15/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNITS 28 AND 43 FINAL APPROVED
08/14/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/13/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
28 -- WATER NOT ON AT KS. CHINA BOWL CAPS MISSING.
ADJUST WATER TEMP AT TUB/SHWR DIVERTOR
TEF TAPE ON CO PLUGS

43 -- TEF TAPE ON CO PLUGS, SUPPORT CLEANOUT
REMOVE 2ND HB
PROVIDE BETTER ACCESS TO SOVS UNDER LAV
HB VAC B AT LAUNDRY
08/11/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) FINAL ONLY UNIT
08/09/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNITS #30 AND #32 FINAL OK
08/07/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/03/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNIT 32 N/R
UNIT 31 OK - WATER TEST CONNECTION
UNIT 42 OK
08/02/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNIT 37 FINAL OK
UNIT 31 AND 42 HAVE FERNCO COUPLINGS VISIBLE
08/01/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
#27 FINAL INSP. OK
07/26/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNIT 29 OK
USE PIPE SUPPORTS ON DRAIN PIPING NOT P TAPE
USE TEF TAPE ON CO PLUGS
07/21/2007 PLUMBING - FINAL Not ready for Inspection SPECIAL INSP. PAID W/CHK#1201

SEAL KS CONNECTION TO COUNTER (CAULK)
KS REQUIRES CLEANOUT
SECURE PIPES
PROVIDE CORRECT BACKFLOW PROTECTIONS FOR IRR
OR REMOVE UNAPPROVED CONNECTION
07/20/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNIT 39 -- FINAL OK
UNIT 32 -- SECURE PIPING AND INSTALL CO
02/09/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNIT 41 OK FOR FINAL

STEVE 406-3632
02/07/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNIT 91: INSTALL CLIPS ON KIT SINK, MAKE CONNECTION TO COUNTER WATER TIGHT
2) MAKE CLEANOUT PLUG WATER TIGHT
3) SECURE DW HOSE, POSITION SO AS NOT TO TRAP FOOD
4) PROVIDE ACCESS PANEL TO TUB WASTE
5) CORRECT DRIP UNDER LAVE
6) CORRECT DRIP AT HB