Permit: T05CM04759

Parcel: 11006159B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINAL 33, 34, 35, 36 S.T.O.I
CHECK 30 & 39?
12/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING SMOKE DETECTORS
2. MISSING EXHAUST FANS
11/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
09/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #43 SUBJECT TO OTHER INSPECTORS
08/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
#43
1. KITCHEN GFCI NOT WORKING ALSO OUTSIDE
2. CLEAN EXCESS DIRT FROM PANEL
3. ARE BOTH KITCHEN CIRCUITS ON THE SAME POLE AND WHERE ARE BEDROOM RECEPTACLES
4. PO PLANS CALL FOR LIGHT AT SIDE DOOR AS PER 210.70
08/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK #28 STOI
08/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK #32
08/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/06/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED CK#1214 FOR $108.00

OK #42
08/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 31
07/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNIT #29 SUBJECT TO OTHER INSPECTORS
07/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/21/2007 ELECTRIC - FINAL Denied RECEIVED CK#1201
FOR $432.00

ALL ROOF UNITS - CHECK IDENTIFICATION OF UNGROUNDED CONDUCTOR, SUPPORT OF SEALTITE, LOOSE FITTINGS AND LABELING OF UNITS.

#27 -- OK INTERIOR

#29 --
A. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
B. INSTALL NEUTRALS TO NEUTRAL BAR - USE APPROVED COPPER TO ALUMINUM SPLICES
C. SEPARATE GROUND & NEUTRAL A/C JUNCTION BOX

#32 --
A. PROTECT CABLE/CORD FROM SHARP METAL EDGES - HOOD
B. MOUNTING SCREW FOR COVER NOT AN APPROVED GROUNDING METHOD
C. BOXES MORE THAN 1/4" FROM BOX TO SURFACE

#42
A. OUTSIDE RECEPTACLE NOT GFCI PROTECTED
B. BOXES MORE THAN 1/4" FROM BOX TO SURFACE
C. IS THERE A COVERED JUNCTION BOX FOR BATH LIGHT

#37
A. BOXES MORE THAN 1/4" FROM BOX TO SURFACE
B. MISSING SMOKE DETECTORS HALL & BEDROOM
C. LABEL PANEL AS PER 408.4
02/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNIT #41

1. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
02/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/04/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINAL APT #211
07/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
#405
1. TIGHTEN LOOSE FITTINGS
2. SWITCHES TO BE GROUNDED
3. SUPPORT SEALTITE
4. MISSING DEAD FRONT COVER A/C DISCONNECT
5. SPLIT BOLT LISTED 2 CONDUCTORS
6. A BOND BUSHING IS NEEDED 250.92