Permit: T05CM04756

Parcel: 130083180

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/18/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/12/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT BEND GAS PIPING-MUST USE COMBINATION OF FITTINGS TO CHANGE DIRECTION
2) MUST PRIME AND WRAP ALL JOINTS
3) MINIMUM 12" DIRT COVER REQUIRED
4) MUST USE APPROVED FITTINGS
5) HAVE PLANS/PERMIT AT PLUMBING PIPING LOCATION
6) STOPPED INSPECTION
09/27/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*