Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 10/12/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT BEND GAS PIPING-MUST USE COMBINATION OF FITTINGS TO CHANGE DIRECTION 2) MUST PRIME AND WRAP ALL JOINTS 3) MINIMUM 12" DIRT COVER REQUIRED 4) MUST USE APPROVED FITTINGS 5) HAVE PLANS/PERMIT AT PLUMBING PIPING LOCATION 6) STOPPED INSPECTION |
|
| 09/27/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* |