Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* LOCKED 1 PM |
|
| 06/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR WILL RESCHEDULE WITH RAY. |
|
| 05/23/2006 | ELECTRIC - FINAL | Denied | 1. 600 AMP. STARTER FOR WELL MUST BE LISTED AS SUITABLE FOR SERVICE SINCE ITS BEING USES AS A MAIN DISCONNECT 2002 NEC 230.66 2. 30A FUSED DISCONNECT FOR PANEL IS ALSO A MAIN, ITS LISTING REQUIRES A NEUTRAL KIT BE INSTALLED IN IT WHEN USED AS A SERVICE MAIN. 3. SURGE APPESTOR DOES NOT HAVE A POINT TO TERMINATE IN, VERIFY WITH C OF T WATER DEPARTMENT ENG. 4. OUTSIDE LIGHTS FOR FINAL. |