Permit: T05CM04691

Parcel: 130010050


Addresses:

2965 E FAIRLAND SV


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM04691

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
SITE SEWER FROM PUBLIC MANHOLE 21' OF DUCTILE IRON INSTALLED.
10/09/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
08/03/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
07/18/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PRE-SLAB FOR FLOOR SINKS & DRAIN
07/13/2006 PLUMBING - ROUGH, SOIL Partial Approval 1. 03057 -- SITE SEWER REQUIRES PCDEQ INVOLVEMENT, SHALL HAVE THERE STAMPED APPROVED PLAN WITH CITY APPROVAL ON PLAN ON SITE. THIS SHALL HAVE AUTHORIZATION FOR CONSTUCTION & FOR COMPLETION, AUTHORIZATION TO DISCHARGE. CITY INSPECTORS & INDEPENDENT INSPECTORS BOTH SHALL INSPECT SITE SEWER.
2. DEW 100 PSI TEST 4" PER REDLINE DRAWN ON SITE NEED REVISED CITY APPROVED PLANS.
3. PROCESS PIPING
2 - 2" STEEL 100 PSI TEST (BINS PIPE) (PLANT PIPE)
1 - 1 1/2" 100 PSI TEST (SAW PIPE)
1 - 4" 100 PSI TEST (BATCH PIPE)
4. NEED TO SEE PIPE MATERIAL TYPE FROM ENGINEER FOR PROCESS PIPING.
06/09/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
BUILDING DRAIN CONNECTIONS TO SEWER
OK TO COVER
CLOSET FLANGES EAST RESTROOMS OK
06/08/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
3" CAST IRON FROM COL. B TO SUMP PP501 - OK
2" CARBON STEEL PUMP DISCHARGE TO SETTLEMENT POND OK
PROVIDE STAMPED LETTER FROM ENGINEER CONFIRMING MATERIAL TYPE.
05/12/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
THIS IS A BELOW SLAB WATER PIPING INSPECTION.
1 1/2" COPPER W/BRAZED JOINTS AND 1 1/2 BLACK STEEL PIPING INSTALLED ALONG COL X2 AND BETWEEN COL. 27-30 THIS IS PROCESS PIPING - PROCESS PIPING IS TO BE INSPECTED BY MECHANICAL INSPECTOR.
PROVIDE DOCUMENTATION FOR MATERIAL TYPE.
05/09/2006 PLUMBING - ROUGH, SOIL Cancelled CANCELLED PER FRED
05/05/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
3 FDS OK
04/24/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PRE-SLAB INSPECTION OK
PROTECT + LEVEL FDS
NOTE: MAIN WASTE LINE OUTSIDE OF SLAB HAS NOT YET BEEN INSPECTED.
04/10/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FLOOR DRAIN AT COL. 19 AND
FLOOR SINK AT COL. 16 OK
04/03/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
DWV BELOW GRADE W/10' WATER TEST OK
CALL FOR PIPE WRAP INSPECTION AND TRAP PRIMERS