Permit: T05CM04672

Parcel: 12213221B


Addresses:

3966 E PIMA ST 02


Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T05CM04672

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
12/19/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*I NEED TO SEE THE BOND BETWEEN GAS AND WATER
PAINT VENT TERMINARS
BREAK OFF AIB RETAINING SCREW
ADA WATER CLOSET-FLUSH HANDLE ON WIDE SID E
WASHER BOX TRIM.
12/19/2005 PLUMBING - FINAL Approved IVRS - Inspection :**PLBG FINAL IS OK
OK FOR C OF O
12/16/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*ALL EXPOSED EXTERIOR WATER PIPING REQUIRES PROTECTION AGAINST THERMAL EXPANSION
HOSE BIBS REQUIRE AVB'S
INSTALL ALL TRIM, COVERS, PLATES, ETC.
CAPPED OFF PIPING INTERFERES WITH OPENING OF CABINET DOOR.
INSPECTION STOPPED.
12/12/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*SHALL PROVIDE PERM CAPS ON ALL FUTURE DRAIN THAT ARE STUBBED OUT OF WALL.
SHALL PROVIDE AN EXPANSION TANK @ WATER HEATER AND STRAP IT DOWN TO WALL.