Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM04672
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/26/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/24/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CONNECTORS NEEDED FOR METAL BOXES 2) SUPPORT NM CABLE WITHIN 12" OF EXHAUST FANS 3) MOVE NM CABLE OUT OF STUD CHANNEL OR PROTECT BOTH SIDE FULL LENGTH OF CABLE RUN 4) CABLE NOT TO BE SUPPORTED OFF OF CABLE 5) SUPPORT NM CABLE 12" + 8' AS PER CODE THHN AND COPPER WIRE NOT SUPPORTING METHODS 6) SUPPORT VDV CABELING AS PER 72536 AND 800.6 7) FINISH DEMO |