Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/05/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FHA OVERBORED TOP PLATES AT GAS, MASTER AND KITCHEN 2) SECURE WALL AT STOVE 3) MOVE PEX FROM MASTER CAN 4) SUPPORT HALL BATH VENT 90 DEGREE 5) FINISH CONDENSATE 6) DWV AND H20 OK 7) OK TO INSULATE |
|
| 12/30/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) TRUSS BRACE CUT/MISSING 2) A/C SECONDARY MUST DRAIN IN A CONSPICOUS LOCATION 3) NO DWV WATER TEST 4) MECH DUCT RESTRICTED AT FRONT BEDROOM 5) NAIL PROTECT PLUMBING 6) PEX WITHIN 12" OF RECESSED LIGHTS 7) SHEAR BLOCK MISSING 8) 5/DT1 NOT COMPLIED WITH 9) STOPPED INSPECTION-TOO MANY ITEMS |