Permit: T05CM04625

Parcel: 13408278G


Addresses:

8401 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/24/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
HEAT STRIP REMOVED -- UNIT FUNCTION STRAIGHT HEAT PUMP -- CORRECTLY FUSED & ID'D
08/31/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MARK THE UNIT DATA PLATE THE WAY THE MANUFACTURER SAYS TO BY SCRATCHING OUT THE BLACK BOX NEXT TO THE PROPER HEAT STRIPS INSTALLED. DO NOT USE ANY INK.
A 5KW 240 VOLT HEAT STRIP IN THAT UNIT REQUIRES A 45 AMP. CIRCUIT. WIRE SIZE & FUSE SIZE ARE NOT ADEQUATE. IF YOU REMOVE THE HEAT STRIP, MARK "NONE" & FUSE ACCORDINGLY.
06/21/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
MARK THE UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. PLANS REQUIRE 5 KW
PROVIDE A FRESH AIR INTAKE.
BLOCK & CLAMP CONDENSATE DRAIN ON ROOF.
01/10/2006 MECHANICAL - FINAL Cancelled
01/10/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*