Permit: T05CM04555

Parcel: 127082020


Addresses:

5311 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/17/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CONTRACTOR FINISHED ITEM FROM INSPECTION DATED 1/13/06
01/13/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*CLEAN SURFACE UNDER LUG 250.12
SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8
INSTALL MAIN BONDING JUMPER SCREW
A BOND BUSHING IS NEEDED IN GUTTER ON NIPPLE 250.92
WHERE ARE LUG TERMINATIONS FOR SERVICE CONDUCTORS
OK TO CLEAR METER # 2
12/09/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TCO WAITING ON A/C UNIT CALCULATIONS AND DRAWINGS
12/08/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROTECT CONDUCTORS AT FITTING #4 & LARGER
2. X-RAY M/C CABLE TO TERMINATE
3. MAINTAIN WORKING CLEARANCES IN FRONT OF DISCONNECTS
4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING.
6. FINISH ROOF
7. PLANS NOT REFLECTIVE OF SERVICE INSTALLED ALSO NEED REVISION STAMP
12/07/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*