Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*OK WALLS ONLY | |
| 10/31/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*PROTECT M/C CABLE IN CHANNEL OF STUDS OR MOVE OUT 300. 4 ALSO AT TOP PLATES FILL UNUSED OPENINGS IN BOX PROTECT PVC CONDUIT AT BASE PLATES SUPPORT M/C CABLE WITHIN 12" OF BOXES AND 6' ON HORIZONTAL PROTECT VDV CABLES FROM SHARP METAL EDGES AND SUPPORT AS PER CODES SUPPORT M/C CABLE IN HARD CEILINGS SUPPORT CONDUITS WITHIN 3' OF EXISISTING SLAB PLEASE PREVENT DIE ELECTRIC CONTACT 'PROVIDE LETTER FROM ENGINEER FOR NOTES ON M/C CABLE AND # 10 BOND CONDUCTOR. |