Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 10/14/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999*PVC IS NOT AN ALLOWED WIRING METHOD FOR CONDUITS IN PATIENT TREATMENT CARE AREAS. SEE ART 517 FOR ASSISTANCE IN WIRING METHOD |