Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NO UFER INSP. INSTALL GROUND RODS PER 250 NEC |
|
| 10/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* COMPLETE AS PER NOTES LAST INSP. |
|
| 04/21/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1. MC CABLE CANNOT BE INSTALLED INSIDE METAL STUD CHANNEL WERE WITHIN 1 1/4" FROM FRONT OF STUD. 2. COMPLETE CONDUIT & MC CABLE INSTALLATIONS, SOME BOXES NOT PIPED IN YET. A RE-INSP. FEE IS ASSESSED PER NOTE INSPECTION 3/28/06. 3. PAY REINSPECTION FEE AT 201 N. STONE |
|
| 04/21/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTE: NO JUNCTION BOXES ABOVE CEILING. JUNCTION BOX TO BE ACCESSIBLE. CEILING DOES NOT SUPPORT WEIGHT. VDV CABLING TO BE AS PER 725.6 & 800.6 NO MORE THAN 360 DEG. IN BEND OF CONDUIT. 1. LEAVE WALL OPEN TO SEE PANEL HOME RUNS OK WALLS ONLY NO CEILINGS RECEIVED MONEY ORDER #55316547033 FOR $108.00 AFTER HOURS INSPECTION. |
|
| 04/20/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/18/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES |
|
| 04/12/2006 | ELECTRIC - INTERMEDIATE | Cancelled | CANCELLED PER CONTRACTOR BRENT #891-0585 | |
| 04/12/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/07/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCEL PER LEE RAY |
|
| 04/06/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCEL PER LEERAY |
|
| 03/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* A REINSPECTINO FEE WILL BE ASSESSED NEXT INSP. IF NOT COMPLETE & CONDUITS, CABLES SUPPORTED PER CODE |
|
| 01/26/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/24/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT CONDUIT PER CODE 2) SUPPORT AND TERMINATE MC PER CODE 3) COMPLETE ROUGH IN |
|
| 01/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NOT READY - RACEWAYS NOT COMPLETE 2. SUBMIT PLAN REVISIONS TO CITY W/NEW SINGLE LINE DIAGRAM |