Permit: T05CM04451

Parcel: 12417053A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/23/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NO UFER INSP. INSTALL GROUND RODS PER 250 NEC
10/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
COMPLETE AS PER NOTES LAST INSP.
04/21/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1. MC CABLE CANNOT BE INSTALLED INSIDE METAL STUD CHANNEL WERE WITHIN 1 1/4" FROM FRONT OF STUD.
2. COMPLETE CONDUIT & MC CABLE INSTALLATIONS, SOME BOXES NOT PIPED IN YET. A RE-INSP. FEE IS ASSESSED PER NOTE INSPECTION 3/28/06.
3. PAY REINSPECTION FEE AT 201 N. STONE
04/21/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTE: NO JUNCTION BOXES ABOVE CEILING. JUNCTION BOX TO BE ACCESSIBLE. CEILING DOES NOT SUPPORT WEIGHT.
VDV CABLING TO BE AS PER 725.6 & 800.6 NO MORE THAN
360 DEG. IN BEND OF CONDUIT.
1. LEAVE WALL OPEN TO SEE PANEL HOME RUNS
OK WALLS ONLY NO CEILINGS
RECEIVED MONEY ORDER #55316547033 FOR $108.00
AFTER HOURS INSPECTION.
04/20/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/18/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES
04/12/2006 ELECTRIC - INTERMEDIATE Cancelled CANCELLED PER CONTRACTOR BRENT #891-0585
04/12/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/07/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCEL PER LEE RAY
04/06/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCEL PER LEERAY
03/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
A REINSPECTINO FEE WILL BE ASSESSED NEXT INSP. IF NOT COMPLETE & CONDUITS, CABLES SUPPORTED PER CODE
01/26/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/24/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT CONDUIT PER CODE
2) SUPPORT AND TERMINATE MC PER CODE
3) COMPLETE ROUGH IN
01/10/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NOT READY - RACEWAYS NOT COMPLETE
2. SUBMIT PLAN REVISIONS TO CITY W/NEW SINGLE LINE DIAGRAM