Permit: T05CM04385

Parcel: 130060060

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
04/03/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
02/17/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1 1/2 TYPE L COPPER FROM 6" PRIVATE MAIN WITH 1 1/2 RP AND 1" BRANCH LINES TO EXTERIOR HBS ON SHADE STRUCTURE AND A 1" SUPPLY TO TRAILER.
- PIPING MEETS CODE BUT PLAN SHOWS ONLY A 2" SUPPLY W/ A 2" PER PLAN.
- PLAN DOES NOT SHOW THE 1" SUPPLY LINES. RED LINE THIS INSTALLATION OK TO COVER 1".
- PROVIDE PROTECTION BETWEEN CU AND STEEL AT HB LOCATIONS
- PROVIDE BACKFLOW CERTIFICATION.