Permit: T05CM04308

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/03/2006 FRAMING Approved IVRS - Inspection :*
OK TO SHEETROCK
02/23/2006 FRAMING Partial Approval IVRS - Inspection :*
1) EXTERIOR WALLS OK, NEED TO FINISH INTERIOR
02/22/2006 FRAMING Partial Approval IVRS - Inspection :*
INTERIOR FRAMING OK -- NEED STAMPED LETTER FROM ARCHITECT REFLECTING CHANGE IN WALL HEIGHTS @ 4B WALLS
1. NEED CORRECT ANCHOR BOLT SPACING @ EXTERIOR SHEAR WALLS
2. CHECK WATER CLOSETS
02/16/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
NEED HOLDDOWNS @ PROPER LOCATIONS FOR SHEAR WALLS
PER FOUNDATION PLAN, SHEET S2.0
02/14/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1. NEED ANCHOR BOLTS WITHIN 12" OF EACH SIDE OF SPLICES AND AT ENDS.
2. ANCHOR BOLTS @ SHEAR WALLS (SW2 & SW3) TO FOLLOW SPACING PER SCHEDULE.