Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NOTE -- LETTER RECEIVED 2/16/06 |
|
| 01/27/2006 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C OF O PER PHONE CALL | |
| 01/25/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED PLAN REVISION LETTER 2) COOLER OUTLET ENCLOSURES STILL DO NOT HAVE PROPER CLEARANCE NEC 110.26 3) TIGHTEN GROUND CONNECTIONS IN "A" AND "B" MAIN SWITCHES NEC 250 4) 125V SHOP OUTLETS NEED GFI PROTECTION NEC 511.12 |
|
| 01/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 12/28/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |