Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2006 | ELECTRIC - PROGRESS | Approved | ||
| 01/19/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/28/2005 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 12/21/2005 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The service is not per code.| 210*NEED TO BOND SERIVCE RISERS SIZE GROUNDING ELECTRODE TAPS TO EACH DISCONNECT PER NEC 250.64 (D) BOND ALL NIPPLES AND RACEWAYS FOR SERVICE IDENTIFY SERVICE DISCONNECTS RUN NEUTRAL TO ALL DISCONNECTS NEC 250.24 BOND ALL METAL PIPING AND BUILDING STEEL TO SERVICE |