Permit: T05CM04237

Parcel: 11519024C


Addresses:

1790 W SAHUARO DR

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
01/19/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
12/28/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) NEED MINIMUM #4 CU GROUND TAP TO PANEL "C" DISCONNECT
2) NEED MINIMUM 2/0 CU TO BOND BLDG STEEL AND METAL PIPE SYSTEMS
12/23/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
12/09/2005 ELECTRIC - UNDERGROUND Cancelled IVRS - RI canceled
11/03/2005 ELECTRIC - UNDERGROUND Partial Approval OK TO COVER SECON. TO EX STUGS @ SLAB STAY @ 24" DEEP
10/25/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*1 2-3" PVC SERVICE TO TRANS
1-3" PVC SERVICE TO EXIST BLD SERVICE