Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/24/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CORRECTIONS ARE ONGOING. CALL FOR FINAL INSPECTION AFTER CORRECTIONS ARE COMPLETE AND ALL EQUIPMENT HAS BEEN INSTALLED. OK TO OCCUPY BUILDING. |
|
| 07/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE PROPER WORKING CLEARANCE FOR DISCONNECTS AND SERVICE EQUIPMENT -- NEC 110.26 2. PROVIDE ILLUMINATION FOR SERVICE EQUIPMENT -- NEC 110.26 (D) 3. PROPERLY IDENTIFY PANEL DIRECTORIES -- NEC 408.4 4. PROVIDE SIGN AT SERVICE FOR GENERATOR -- NEC 701.9 5. EMERGENCY LIGHTING IS NOT PER PLAN (LOWER LEVEL NORTH HALL) 6. IDENTIFY ALL EMERGENCY EQUIPMENT PER NEC 700.9 (A) 7. THERE ARE SEVERAL PIECES OF EQUIPMENT YET TO BE INSTALLED. EACH TO BE LISTED AND WIRED PER LISTING NEC 110.3 8. ALL ROOFTOP MECHANICAL EQUIPMENT NEEDS TO HAVE A DISCONNECTING MEANS AND PROPERLY SIZED BRANCH CKT NEC 220 AND 430.102, NEC 110.3 |
|
| 07/20/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |