Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 04/17/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. IF TRANSFER SWITCH HAS SOLIDLY CONNECTED NEUTRAL, NO GROUNDING ELECTRODE IS NEEDED FOR THE GENERATOR, SINCE IT WILL NOT BE A SEPARATELY DERIVED SYSTEM. IN THIS CASE, YOU MUST REMOVE GENERATOR BONDING JUMPER. YOUR UFER MAY BE CONNECTED TO GENERATOR GROUND, AS LONG AS IT (OR THE GROUNDS) MAKE NO CONNECTION TO NEUTRAL IN GENERATOR. |
|
| 03/27/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER 10-3/4" PVC |
|
| 03/24/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* REMAINDER INTERIOR LOWER LEVEL. |
|
| 03/21/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER 2ND FLOOR -- FLOOR OUTLETS (4) |
|
| 02/23/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*PIPE WRAP IN GROUTED | |
| 02/15/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) NOTE: NEED TO WRAP EMT USED IN GROUTED WALLS OR YOU MAY USE EMT AS A MC OR AC CHASE NEC 300.6 (B) |
|
| 01/12/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER SECONDARY CONDUITS (X-FORMER TO SERVICE - 3 4"PNC) |
|
| 12/30/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*OK TO COVER UFER ( 20' BARE) | |
| 12/29/2005 | ELECTRIC - UNDERGROUND | Cancelled | CANCELLED PER SUPERINTENDENT DAN #275-0428 | |
| 12/29/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* |