Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM04146

Parcel: 140430130

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T05CM04146

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2007 MECHANICAL - HOODS Approved IVRS - Inspection :*
01/24/2007 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSULATION ON ACCESS DOORS NOT INSTALLED CORRECTLY
READ INSTALL INSTRUCTIONS
CHECKED HYDRONIC PIPING ON ROOF 100 PSI OK TO INSULATE
01/17/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1ST LAYER FIRE WRAP OK TO PROCEED
01/11/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDED GREASE DUCTS
1 ACCESS DOOR NOT TIGHT
OK FOR 1ST LAYER OF FIRE WRAP