Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM04146
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* NOTES: 1. FLEX CONDUIT MUST BE SUPPORTED PER CODE USE OWN SUPPORT WIRES 2. COMPLETE WIRING, J-BOX MAKEUP, FIXTURES 3. CAN LIGHTS NEED ADDITIONAL SUPPORT OTHER THAN SET SCREW CONNECTOR - HAVE ARCH. ADDRESS INSTALLATION. 4. OK NORTH & SOUTH ENTRANCE SOFFITS 5. GROUNDS TO BOND BUSHINGS TO SMALL, SIZE PER CODE. |
|
10/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS EXCEPT CANOPY OUTSIDE. |