Permit: T05CM04138

Parcel: 12108063A


Addresses:

1519 N WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/27/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
06/22/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- WATER TEST DWV OK
- PROVIDE GRN TRACER WIRE ON EXTERIOR NON-METALLIC PIPING.
- REDLINE LOCATION OF DRAIN PIPING CONTRARY TO PLAN.
- SUPPORT HORIZONTAL ABS ABOVE CEILING.
- SECURE VERTICAL ABS IN WALL.
- WATER TUBING NOT INSTALLED PER PLAN.
- TYPE L COPPER SPECIFIED.
- SECURE WATER PIPING IN WALL, SUPPORT OVERHEAD
- PROVIDE LADDER TO ACCESS OVERHEAD PIPING.