Permit: T05CM04138

Parcel: 12108063A


Addresses:

1519 N WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/21/2006 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
1) STRAP CONDUCTOR TO BLDG
09/20/2006 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
SPLICES TO BE IRREVERSIBLE -- 250.64
09/19/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn
1. GROUNDING ELECTRODE CONDUCTORS FOR SERVICES MISSING.
INTERIOR OK.