Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* 1) STRAP CONDUCTOR TO BLDG |
|
| 09/20/2006 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* SPLICES TO BE IRREVERSIBLE -- 250.64 |
|
| 09/19/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode conn 1. GROUNDING ELECTRODE CONDUCTORS FOR SERVICES MISSING. INTERIOR OK. |