Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
04/06/2007 ELECTRIC - UFER Approved IVRS - Inspection :*
04/05/2007 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND CLAMP TO BE LISTED & MARKED FOR DIRECT BURY AND REBAR SIZE -- NEC 250.70
2. INSTALL CLAMP PER MANUFACTURES INSTRUCTIONS.