Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
| 01/24/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NEED RETROS ON 6 HOLDOWNS DUE TO SPALDING IN FOUNDATION: SW CORNER GARAGE, FRONT N.W. BEDROOM, S.E. CORNER DINING ROOM AND 3 AT EAST MASTER BEDROOM 2) OK TO RUN WIRE LATHE WILL INSPECT AT INTERMEDIATE |
|
| 01/08/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CHANGE FROM 12/18/06 2) ROOF DRIED IN WITHOUT INSPECTION 3) YOU MUST PROVIDE OSHA APPROVED LADDER ACCESS TO ROOF |
|
| 12/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) TRUSSES MUST BEAR AT MID POINT ON 3 PT BEARING WALL ENTRY 2) NO CITY OF TUCSON APPROVED TRUSS DRAWINGS ON SITE 3) AV1GE NOT BEARING AT POINT 21 4) AV TRUSSES NOT BEARING AT DT 17 5) AV TRUSSES INSTALLED IN AV1 LOCATIONS. PROVIDE CITY APPROVED TRUSS ENGINEERS REPAIR 6) PROVIDE CITY APPROVED DETAIL FOR SHEARWALL CONNECTION TO TRUSS SYSTEM AT PATIO 7) SHEARWALL 2 REQUIRES EDGE NAILING AT 4" ON CENTER 8) HOLDOWN REQUIRE 16D NAILS NOT GUN NAILS 9) CLIP GABLE END TRUSSES |