Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/10/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AIR BALANCE REPORT |
|
| 04/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AN ACCESS DOOR & ANGLES AROUND FIRE DAMPER IN CONTROL ROOM & NEW ELEC. ROOM TESTED DAMPERS OK FOR TEMP C OF O |
|
| 03/30/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DO NOT TERMINATE PRIMARY DRAIN INTO A TRAP FROM ANOTHER UNIT. TERMINATE SECONDARY DRAINS TO BE A CONSPICUOUS LOCATION. ROOFTOP EQUIPMENT OK. |