Permit: T05CM03285

Parcel: 12111022A


Addresses:

4927 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/25/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
PIPING CAPPED AT DF PER PLAN REVISION OF 6/25/07
FUTURE INSTALLATION OF BEVERAGE DISPENSER WILL REQUIRE A PERMIT
07/23/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
-- YOU HAVE A TAPPED C O PLUG ALLOWING SEWER GASES INTO BUILDING
-- BACKFLOW CERT FOR IRR RECEIVED
-- BACKFLOW CERT NEEDED FOR WORK DONE TO SERVICE PROTECTION RP AFTER 5/31/07
-- REVISION OK FOR FUTURE WATER COOLER OK
05/31/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL DF
RAISE RP DEVICE TO 12" ABV FLOOD LEVEL OF NEW CURB
RETEST RP DEVICE
INSTALL HB VAC BREAKER AT HB
CORRECT PIPING AT IRRIGATION ASSEMBLY PROVIDE CERT.
04/10/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
NO PLUMBING PROBLEMS EXIST THAT WOULD PREVENT TCO
03/30/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. NOT READY FOR FINAL.
2. NEED TO CLEAR ROUGH SOIL AND SEWER.
3. PROVIDE APPROVED PLAN REVISIONS REQUESTED
ON 7/18/06 7/21/06 AND 7/24/06
4. NEED DF INSTALLED FOR FINAL
5. NEED TO INSTALL CLEANOUT SCREW AT MISSING DF PRIOR TO TCO
6. HB VAC BREAKER INSTALLATION