Permit: T05CM03285

Parcel: 12111022A


Addresses:

4927 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/26/2007 PLUMBING - ROUGH, SOIL Approved
12/26/2006 PLUMBING - ROUGH, SOIL Cancelled CANCELLED PER DELMA
08/03/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FDS, TRAP PRIMERS AND WRAPS IN PLACE FOR CONCRETE
PROVIDE P-2 REVISION FOR APPROVAL OF ROUGH
07/24/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
UNDERGROUND DWV INSTALLED PER REDLINE REVISIONS
FINAL APPROVAL REQUIRES PLAN REVISION
07/21/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection PROVIDE REDLINE ON SITE OF YOUR INSTALLATION WITH TEST IN PLACE. WITH REVISED CITY APPROVED PLAN TO FOLLOW.
07/18/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4" BUILDING SEWER FROM EXISTING TO CLEANOUT PER REDLINE ON SITE 8 1/2 X 11 MY INITIAL WATER TEST PARTIAL.
1. WILL NEED REVISED CITY APPROVED PLAN. PROVIDE TRACER WIRE.
2. WILL NEED INFORMATION SUPPLIED WITH REVISION FOR NEED OF BACKWATER VALVES IF REQUIRED.

1" WATER ALSO FROM EXISTING TO BUILDING ENTRY OK.