Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING JUNCTION BOX COVER 2. PROVIDE PHYSICAL PROTECTION AND PREVENT TRIPPING HAZARD FOR GROUND CONDUCTOR ON ROOF 3. FINISH PREVIOUS ITEMS #1, 2, 3 4. UNIT IS OCCUPIED AND IN OPERATION WITHOUT FINAL INSPECTIONS. |
|
| 05/31/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SECURE CABLES TO CABLE TRAY UPON EXIT 2. FINISH VDV CABLING CONTROL ROOM 3. TIGHTEN LOOSE FITTINGS 4. BOND LIGHTING CONTACTOR ENCLOSURE 5. VERIFY PERMIT FOR INSTALLATION OF BATTERY ROOM EQUIPMENT. 6. MOVE SATELLITE DISH FOR CLEARANCES TO A/C'S |
|
| 03/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TCO FOR MONITOR OF EQUIPMENT |
|
| 02/13/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FIRE ALARM BOXES MAY NEED EXTENDER RINGS OK RECEPTACLES ROOMS 100-105 OK TO USE ROOM 105 |