Permit: T05CM03285

Parcel: 12111022A


Addresses:

4927 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/26/2007 ELECTRIC - ABOVE CEILING Approved
03/26/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK PREVIOUS ITEMS EXCEPT AS NOTED ROOM 100-102, 108
2) HAVE ENGINEER DEFINE IF ROOM IS A PLENIUM 300.22 (B) OR ENVIORMENTAL AIR 300.22 (C)
3) NOTE: VERIFY IF VDV CABELING IS RATED FOR SPACE
03/23/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. USE APPR FITTING WITH L.B - CHASE NIPPLE NOT APPROVED AC 1
2. SUPPORT CONDUIT - AC 1
3. SUPPORT WIRES NEEDED FOR EXIT LIGHTS
4. CANNOT STRIP SEAL TITE OF JACKET
5. FLUSH #5 OF PREVIOUS INSPECTION.
03/20/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT WIRES NEEDED FOR CANS
2. WIRING IN PLENUM CEILING TO BE FOR ENVIRONMENTAL AIR 300.22
3. WE HAVE BOX OVERFILL
4. TIGHTEN LOOSE FITTINGS
5. CONDUIT OVER 4' PER CODE NOT ALLOWED 300.22
6. LABEL DISCONNECT ABOVE CEILING RM 100
7. INSTALL EXIT LIGHTING
8. ATTACH FIXTURES TO GRID 410.16