Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
| 03/26/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK PREVIOUS ITEMS EXCEPT AS NOTED ROOM 100-102, 108 2) HAVE ENGINEER DEFINE IF ROOM IS A PLENIUM 300.22 (B) OR ENVIORMENTAL AIR 300.22 (C) 3) NOTE: VERIFY IF VDV CABELING IS RATED FOR SPACE |
|
| 03/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. USE APPR FITTING WITH L.B - CHASE NIPPLE NOT APPROVED AC 1 2. SUPPORT CONDUIT - AC 1 3. SUPPORT WIRES NEEDED FOR EXIT LIGHTS 4. CANNOT STRIP SEAL TITE OF JACKET 5. FLUSH #5 OF PREVIOUS INSPECTION. |
|
| 03/20/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT WIRES NEEDED FOR CANS 2. WIRING IN PLENUM CEILING TO BE FOR ENVIRONMENTAL AIR 300.22 3. WE HAVE BOX OVERFILL 4. TIGHTEN LOOSE FITTINGS 5. CONDUIT OVER 4' PER CODE NOT ALLOWED 300.22 6. LABEL DISCONNECT ABOVE CEILING RM 100 7. INSTALL EXIT LIGHTING 8. ATTACH FIXTURES TO GRID 410.16 |