Permit: T05CM03285

Parcel: 12111022A


Addresses:

4927 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/26/2007 ELECTRIC - INTERMEDIATE Approved
02/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ROOM 108
ROOF:
1. WHERE AND DISCONNECTING MEANS AND LABELING FOR UNITS.
2. SUPPORT BONDING CONDUCTOR UP OFF OF ROOF.
3. MAINTAIN WORKING CLEARANCES FOR DISCONNECTS 110.26
4. CONDUIT ACROSS ROOF TO BE SUPPORTED.
02/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ROOM 109 - EAST
OK GUTTER & CONDUITS FOR FILL
01/05/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
MEET WITH RICHARD TO DISCUSS GUTTER FILL AND AMPACITY
01/03/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ROOM #109 AT PANELS
OK BATHROOM HARD LIDS FOR ACCESS ROOM #103, 104
12/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) JUNCTION BOXES TO BE ACCESS ABLE ABOVE HARD LIDS
2) OK WALLS AND HARD LIDS ROOM 100, 103, 104, 109 AND 119 SUBJECT TO ACCESS
12/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOM 101-102
12/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. LABEL A/C DISCONNECTS & STARTER
2. MAINTAIN WORKING CLEARANCES

OK CRAC 8 & 9
CRCU 8 & 9
OK GROUND RING SUBJECT TO CERTIFICATION LETTER
OK CONDUITS ROOMS #112, 113, 118
11/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO RE-ENERGIZE POWER
OK CONNECTION OF NEW SECTION
(RICH 520-909-4749)

RECEIVED LETTER OF TORQUE
RECEIVED CHECK #1090 FOR $108.00

* DO NOT ENERGIZE CIRCUITS WITHOUT INSPECTIONS.
10/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
COMPLETION OF GROUND RING & TAILS INCLUDING GROUND RODS EVERY 10', TIED INTO EXISTING GROUND RING WITH TWO TEST WELLS -- OK TO COVER
10/16/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROGRESS
1. OK BATTERY ROOM SURFACE CONDUITS
OK CORRIDOR CONDUITS ON SURFACE
OK MECH ROOM
STARTING GRD. RING AT REAR ADDITION - RODS EVERY 20'
2. PNLS ECP-1, ECP-2, TWO 2" CONDUITS ADDED FROM PNL TO GUTTER TO INCREASE CAPACITY ALLOWANCE AND UPSIZING #12'S TO #10'S AWG FOR CORRECTIONS OF AMPACITY FOR # OF CONDUCTORS IN CONDUITS. OK.
3. 5 - 2 1/2" EMT CONDUITS (PARTIAL OK) FROM MECH. RM. TO AC UNITS.
09/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL MECHANICAL ROOM
OK BOXES IN BLOCK SHIPPING
09/25/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. IDENTIFY FIRE ALARM BOXES
2. PLEASE VERIFY DERATING OF CONDUCTORS PER 310.15
3. CHECK AUXILARY GUTTER REQUIREMENTS 366
4. PLEASE OPEN WALL COVERED WITHOUT INSPECTION

OK WALLS NEW BATTERY ROOM
08/03/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FIBER DUCT WITHIN 20' OF BUILDING
70' FROM FRONT VAULT AND 120' REAR VAULT
07/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLEASE ADD 02010 TO PERMIT

OK 6 - 4" PVC UNDER SLAB OUT TO CURB
OK 3 - 2 1/2" PVC UNDER SLAB OUT TO CURB
OK 3 - 1" PVC UNDER SLAB OUT TO CURB
OK 3 - 3/4" PVC UNDER SLAB OUT TO CURB
WAITING ON REVISION