Permit: T05CM03101

Parcel: 126020230


Addresses:

4656 E 1ST ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/14/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11/06/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
REVISED PLAN TO BE CITY APPROVED SHOWING ALL GAS APPLIANCES IN KITCHEN AREA. TEST SHALL HOLD WITH NO PRESSURE LOSS. ALL APPLIANCES TO BE INSTALLED CORRECTLY FOR FINAL.

(2) RESTROOMS IN SOUTH ASSEMBLY AREA FUNCTIONAL
04/03/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
REVISED APPROVED PLAN ON SITE.
14 PSI AIR TEST FROM METER OVERHEAD TO CAPS AT (2) ROOFTOP UNITS AND TO 1 1/4 SHUT OFF VALVE PRIOR TO ANSUL VALVE - OK
1. NEED TEST ON DOWNSTREAM PIPING OF 1 1/4 VALVE AT ANSUL VALVE AND TO SHUT OFF VALVES ON ROOF. TEST SYSTEM IN ENTIRETY.
2. SECURE GAS PIPING OVERHEAD TO RTU-2
3. PROVIDE BONDING OF GAS PIPING.
02/22/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE CITY APPROVED GAS ISOMETER PLAN OF YOUR GAS INSTALLATION.
2. TEST SYSTEM IN ENTIRETY