Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* APPROVED AS PER REJECTION LISTED BELOW NOTE GUTTER BELOW CEILING 1. GUTTER IN STORAGE ROOM - SE CORNER OF BLDG APPEARS TO HAVE OVER ALLOWED 30 CURRENT CARRYING CONDUCTOR FALLING INTO TABLE 310-15 B-2 FOR DERATING 31-45 CURRENT CARRYING CONDUCTORS AT 35%. 2. THE GUTTER IS UNAPPROVED IT'S IN TWO SECTIONS AND NOT COUPLED WITH A LISTED RING. 3. GUTTER REQUIRED TO BE BONDED TO EQUIPMENT GRID. |