Permit: T05CM03101

Parcel: 126020230


Addresses:

4656 E 1ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/12/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
APPROVED AS PER REJECTION LISTED BELOW
NOTE GUTTER BELOW CEILING
1. GUTTER IN STORAGE ROOM - SE CORNER OF BLDG APPEARS TO HAVE OVER ALLOWED 30 CURRENT CARRYING CONDUCTOR FALLING INTO TABLE 310-15 B-2 FOR DERATING 31-45 CURRENT CARRYING CONDUCTORS AT 35%.
2. THE GUTTER IS UNAPPROVED IT'S IN TWO SECTIONS AND NOT COUPLED WITH A LISTED RING.
3. GUTTER REQUIRED TO BE BONDED TO EQUIPMENT GRID.